Look up the authority declaration and control.set_authority, which set the control authority of an Arc automation.

The authority declaration sets the control authority that an automation starts with. control.set_authority changes it while the automation runs. For how Synnax decides which writer controls a channel, see control authority.

authority

Sets the starting authority of the channels that the automation writes. authority is a keyword, so it needs no import.

Form Effect
authority 200 All write channels start at 200.
authority (200 ch_a 100) ch_a starts at 100. All other write channels start at 200.
authority (ch_a 100) ch_a starts at 100. All other write channels start at 255.
  • Values are integers from 0 to 255. A higher value has priority.
  • An automation without an authority declaration writes all channels at 255.
  • Declarations come after the imports and before all other top-level code, variables included.
  • A program can have more than one declaration, but only one default value and one value for each channel.

Inside the parentheses, a new line or a space separates the entries:

authority (
    200
    press_vlv_cmd 100
    vent_vlv_cmd 150
)

1 -> press_vlv_cmd
0 -> vent_vlv_cmd

set_authority

Changes the authority of one write channel, or of all write channels, while the automation runs. Import it with import control.

valueu8 Required

The new authority, 0 to 255.

channelchan T

The write channel to change. Leave it out to change all write channels.

  • Trigger -> optional. The value must be u8, such as a u8 channel or time.interval. A bool value, such as a comparison, is an error.
  • Output -> none.
  • Runs -> once each time its stage starts. Later trigger values have no effect until the stage starts again. At the top level, it needs an upstream trigger, such as start_cmd -> control.set_authority(value=200), and runs once, on the first trigger value. Without a trigger, a top-level call is a syntax error.

The change goes out before the writes of the same cycle. A value of 0 does not release the channel. The automation keeps control at authority 0 until a writer with a higher authority, or a writer with an equal authority that opened earlier, takes it.

As a step of its own in a sequence, it moves on to the next step after it runs.

import control

authority 100

sequence fill {
    stage pressurize {
        control.set_authority(value=220, channel=press_vlv_cmd)
        1 -> press_vlv_cmd
        tank_pt > 300 => next
    }
    stage hold {
        control.set_authority(value=100)
        0 -> press_vlv_cmd
    }
}

start_cmd == 1 => fill

On a Driver, a known bug affects two or more set_authority calls that run in the same cycle when one of them has no channel. The Driver sends a bad authority change, and the automation stops writing. On a Driver, give every call a channel, or run only one call in each cycle. The Core is not affected.