# `control`

> Look up the authority declaration and control.set_authority, which set the control authority of an Arc automation.

The `authority` declaration sets the control authority that an automation starts with. `control.set_authority` changes it while the automation runs. For how Synnax decides which writer controls a channel, see [control authority](https://docs.synnaxlabs.com/reference/control/authority).

## `authority`

Sets the starting authority of the channels that the automation writes. `authority` is a keyword, so it needs no `import`.

| Form                       | Effect                                                       |
| -------------------------- | ------------------------------------------------------------ |
| `authority 200`            | All write channels start at 200.                             |
| `authority (200 ch_a 100)` | `ch_a` starts at 100. All other write channels start at 200. |
| `authority (ch_a 100)`     | `ch_a` starts at 100. All other write channels start at 255. |

* Values are integers from 0 to 255. A higher value has priority.
* An automation without an `authority` declaration writes all channels at 255.
* Declarations come after the imports and before all other top-level code, variables included.
* A program can have more than one declaration, but only one default value and one value for each channel.

Inside the parentheses, a new line or a space separates the entries:

```arc
authority (
    200
    press_vlv_cmd 100
    vent_vlv_cmd 150
)

1 -> press_vlv_cmd
0 -> vent_vlv_cmd
```

## `set_authority`

Changes the authority of one write channel, or of all write channels, while the automation runs. Import it with `import control`.

* [`value`](https://docs.synnaxlabs.com/reference/control/arc/standard-library/control#set_authority-value)`u8`\* Required

  The new authority, 0 to 255.

* [`channel`](https://docs.synnaxlabs.com/reference/control/arc/standard-library/control#set_authority-channel)`chan T`

  The write channel to change. Leave it out to change all write channels.

- Trigger -> optional. The value must be `u8`, such as a `u8` channel or `time.interval`. A `bool` value, such as a comparison, is an error.
- Output -> none.
- Runs -> once each time its stage starts. Later trigger values have no effect until the stage starts again. At the top level, it needs an upstream trigger, such as `start_cmd -> control.set_authority(value=200)`, and runs once, on the first trigger value. Without a trigger, a top-level call is a syntax error.

The change goes out before the writes of the same cycle. A value of 0 does not release the channel. The automation keeps control at authority 0 until a writer with a higher authority, or a writer with an equal authority that opened earlier, takes it.

As a step of its own in a sequence, it moves on to the next step after it runs.

```arc
import control

authority 100

sequence fill {
    stage pressurize {
        control.set_authority(value=220, channel=press_vlv_cmd)
        1 -> press_vlv_cmd
        tank_pt > 300 => next
    }
    stage hold {
        control.set_authority(value=100)
        0 -> press_vlv_cmd
    }
}

start_cmd == 1 => fill
```

On a Driver, a known bug affects two or more `set_authority` calls that run in the same cycle when one of them has no `channel`. The Driver sends a bad authority change, and the automation stops writing. On a Driver, give every call a `channel`, or run only one call in each cycle. The Core is not affected.