ReferenceControlArcCompute values

Compute values from channels

Convert units, combine sensors, smooth noise, and vote between sensors with Arc.

An Arc automation can compute values from channels and write them to a new channel. Synnax stores the result, and the automation computes it whether or not anything reads the channel. A calculated channel stores nothing and computes only while something streams or reads it. See Arc, calculated channels, or Python.

Before you start, create each output channel, such as tank_pt_kpa. To store it, give it its own new index channel. The automation writes the index too. If the output channel does not exist, the code does not compile.

Each recipe below is a complete program. To run one, create an Arc automation, copy the code, choose a Driver, and click Start.

Convert units

tank_pt * 6.89476 -> tank_pt_kpa

The flow runs for each new tank_pt value. Each result has the timestamp of the value it came from.

Combine two sensors

inlet_pt - outlet_pt -> filter_dp

The flow runs when either channel gets a new value, after both have a first value. It uses the latest value of the other channel.

Compute a rate of change

import math

tank_pt -> math.derivative{} -> tank_pt_rate

math.derivative gives the change per second, from the timestamps of the samples. Its first value is 0.

Smooth a noisy sensor

An exponential moving average follows the sensor but damps its noise:

func ema{alpha f64} (value f64) f64 {
    avg $= 0.0
    first $= true
    if first {
        avg = value
        first = false
    } else {
        avg = alpha * value + (1.0 - alpha) * avg
    }
    return avg
}

tank_pt -> ema{alpha=0.1} -> tank_pt_smooth

A smaller alpha smooths more, but follows changes more slowly. The effect of alpha depends on the sample rate of the sensor. Smooth a noisy sensor before you compute its rate of change: tank_pt -> ema{alpha=0.1} -> math.derivative{} -> tank_pt_rate.

math.avg is not a moving average. It gives one average for each block of samples. See the math module.

Vote between redundant sensors

With three sensors on the same tank, the middle value ignores one failed sensor:

func median3(a f64, b f64, c f64) f64 {
    if (a >= b and a <= c) or (a >= c and a <= b) {
        return a
    }
    if (b >= a and b <= c) or (b >= c and b <= a) {
        return b
    }
    return c
}

median3(tank_pt_1, tank_pt_2, tank_pt_3) -> tank_pt_voted

If one sensor reads 0 while the others read 500, the result is 500. The function runs when any of the three sensors gets a new value, after each has a first value.