ReferenceHardwareModbusRead task

Modbus read task

Read the coils and registers of a Modbus TCP server into channels.

A Modbus read task reads coils and registers from one Modbus server into channels. For example, it can record a tank level from holding registers 0 and 1 of a PLC at 10 Hz.

Before you start, you need a connected server.

Registers and coils

A read task reads four types of data, each with its own address range:

Console label Modbus name Function code Value
Coil Coil 01 0 or 1
Discrete Discrete input 02 0 or 1
Holding register Holding register 03 A number, in 1 to 4 registers
Register Input register 04 A number, in 1 to 4 registers

A register holds 16 bits. An 8-bit or 16-bit value uses one register, and an 8-bit value is the low byte. A 32-bit value uses two registers, and a 64-bit value uses four. The Data type of the channel sets the size.

For each type, the Driver reads all addresses from the lowest to the highest in one request. One request can hold at most 125 registers or 2000 coils or discrete inputs.

The Driver timestamps each read with the computer clock. See timing.

Byte and word order

By default, the Driver reads the low word of a 32-bit or 64-bit value first. Many devices send the high word first. The Swap words switch of the server puts the high word first, and Swap bytes swaps the two bytes in each register. The switches set the order for every register channel of the server.

To change the order of one channel, use its Bytes and Words selects. Each select has three options:

  • device -> uses the switch of the server, and shows its value, such as device (swapped).
  • swapped -> swaps the order of this channel, whatever the server sets.
  • not swapped -> does not swap the order of this channel, whatever the server sets.

The Console hides Words for 8-bit and 16-bit data types, because they fit in one register. In code, leave bytes_swapped and words_swapped unset to use the order of the server.

Create a Modbus read task

Enterprise
  1. In the devices toolbar, right-click the server and select Create read task.
  2. Set Sample rate and Stream rate.
  3. Click Add channel. Select the type, then enter the address. For a register, select the Data type.
  4. Click (Start).

The Console creates the channels. For the server Pump skid PLC, a float32 holding register at address 0 gives Pump_skid_PLC_holding_register_input_0_f32, and a coil at address 3 gives Pump_skid_PLC_coil_input_3. The index channel is Pump_skid_PLC_time.

Task options

Console label Python field Default Notes
Modbus server device The key of the server.
Sample rate sample_rate 10 Hz How often the Driver reads the server. Up to 50,000 Hz.
Stream rate stream_rate 5 Hz See read tasks.
Data saving data_saving_disabled On See data saving.
Auto start auto_start Off Starts the task each time the Driver starts.

Channel reference

Each channel has an address, from 0 to 65535, and a channel, the Synnax channel that records the value. Each table shows the Console label of a setting, with its Python field under it.

Coil

Python CoilReadChannelTypeScript coil

Reads a coil as 0 or 1, as uint8.

Troubleshooting

“Illegal data address”

The server does not have one of the addresses in the task. Check the address map of the device. Some devices count addresses from 1, so try the address minus 1.

“unsupported data type: …”

The Console also lists the boolean, timestamp, and uuid data types, but the Driver does not support them. Select a data type from the channel reference.

“Too many data”

The addresses of one type span more than one request can hold. Move the channels closer together, or split them into two tasks.

The values are wrong

Set the byte and word order of the server or the channel. Check that the data type matches the device.

The task stopped when the connection dropped

The task stops on any connection error. Start the task again when the server is back.

For other problems, see Connect a Modbus server and Troubleshoot hardware.