OPC UA read task

Read the values of OPC UA nodes at a fixed rate and record them in channels.

An OPC UA read task reads the values of nodes on a server at a fixed rate and records them in channels. For example, it can record the tank pressures and pump speeds of a PLC 50 times a second. The Driver times each read in software.

Before you start, you need a connected OPC UA server.

Node IDs

Each channel of the task reads one node. A node ID has the form NS=<namespace>;<type>=<identifier>:

Type Identifier Example
I A number NS=2;I=1001
S A string NS=2;S=Tank1.Pressure
G A GUID NS=2;G=09087e75-8e5e-499b-954f-f2a9603db28a

Write NS and the type in uppercase. The Driver rejects ns=2;s=Tank1.Pressure. The browser in the Console fills the node IDs for you.

Create an OPC UA read task

Enterprise
  1. In the devices toolbar, right-click the server and select Create read task.
  2. Set Sample rate and Stream rate.
  3. In the Browser, expand the folders of the server.
  4. Drag the variables to read into Channels. You can select more than one.
  5. Click (Start).

The Console creates a channel for each node, named from the browse name of the node. To choose a name, edit the name of the channel before you start. The Console also creates an index channel named <server>_time_for_<task>, unless one of the channels already has an index or you use server timestamps.

Read arrays

Some servers buffer fast samples in an array node. To read the arrays:

  1. Turn on Array sampling.
  2. Set Array size to the number of values in each array.

The Driver then reads each node Sample rate / Array size times a second, and spreads the timestamps of the values evenly over the read period. Sample rate must be equal to or more than Array size. Each array must have exactly Array size values, or the Driver drops the frame and shows a warning. Stream rate does not apply in array mode.

Use server timestamps

By default, the Driver gives the values of each read the time halfway through the read request. To use the time from the server instead:

  1. Add a node with a DateTime value, such as the source time of the PLC, to the task.
  2. Turn on Use as index for that channel.

The Driver then uses the value of that node as the timestamp of every channel in the task. Only one channel can be the index.

Task options

Console label Python field Default Notes
OPC UA server device The key of the server.
Sample rate sample_rate 50 Hz (10 Hz in Python) Reads per second. At most 10,000.
Stream rate stream_rate 25 Hz (5 Hz in Python) Frames per second sent to the Core. At most the sample rate. Not in array mode.
Array sampling array_mode Off See read arrays.
Array size array_size 1 Values in each array node.
Data saving data_saving_disabled On See data saving.
Auto start auto_start Off Starts the task each time the Driver starts.

TypeScript uses the same fields in camel case, such as sampleRate. See timing.

Channel reference

The table shows the Console label of each setting, with its Python field under it.

Setting Default Notes
Channel name name Empty The name of the channel that the Console creates.
channel The key of the channel that records the values.
Node ID node_id See node IDs.
Node name node_name Empty The browse name. For display only.
data_type float32 The data type of the channel that the Console creates.
Use as index is_index Off Shows only for a DateTime node. See server timestamps.
Enabled disabled Off A disabled channel is not read.

Data types

The Console creates each channel with the data type of its node:

OPC UA type Synnax data type
Boolean uint8
SByte int8
Byte uint8
Int16 int16
UInt16 uint16
Int32 int32
UInt32 uint32
Int64 int64
UInt64 uint64
Float float32
Double float64
String string
DateTime timestamp
Guid uuid

Troubleshooting

For other problems, see Troubleshoot hardware.