Connect an OPC UA server

Connect an OPC UA server to Synnax, with its login and security settings.

An OPC UA server makes the values of a PLC or a SCADA system available as nodes. In Synnax, an OPC UA server is one endpoint with its login and security settings. The read task and the write task add the nodes.

Prerequisites

Supported
WindowsmacOSLinuxNI Linux RTDocker
  • A running Driver that can reach the server on the network. Synnax Desktop runs one for you.

Connect a server

Enterprise
  1. In the devices toolbar, click (Connect device), then select OPC UA server. You can also run the “Connect OPC UA server” command.
  2. Enter a name for the server.
  3. In Endpoint, enter the address of the server, for example opc.tcp://192.168.1.50:4840.
  4. In Connect from, select the Driver that connects to the server. If only one running Driver has OPC UA enabled, the Console selects it for you.
  5. If the server needs a login, enter the Username and the Password.
  6. Set the security.
  7. Click Connect.

The Console asks the Driver to connect to the server before it saves the server. If the test fails or takes more than 10 seconds, the dialog shows the error and keeps your entries.

Security

In the Security section, the Mode and the Policy protect the connection between the Driver and the server. Set them to values that the server accepts.

  • Mode -> None, Sign, or Sign and encrypt.
  • Policy -> the algorithms. The field shows when the mode is not None. When you change the mode from None, the Console selects Basic 256-bit with SHA-256. Select a deprecated policy only when the server supports no other policy.
  • Client certificate and Client private key -> the certificate that the Driver sends to the server, and its key. The fields show when the mode is not None.

In Python and TypeScript, set a policy other than "None" when the mode is not "None". With the policy at "None", the Driver does not load the certificates, even when the mode is "Sign".

The certificate and key are file paths on the computer that runs the Driver:

  • In Synnax Desktop, the Console and the Driver run on the same computer, so the file picker gives a correct path.
  • When the Driver runs on a different computer, the picker gives a path on your computer. Set the paths in Python or TypeScript instead.
  • The Console in a web browser cannot pick files. Set the paths in Python or TypeScript.

In Python and TypeScript, set a policy other than "None" when the mode is not "None". With the policy at "None", the Driver does not load the certificates, even when the mode is "Sign".

The private key must not have a password. The server reads the application URI of the Driver from the URI in the client certificate. Without a client certificate, the URI is urn:synnax.opcua.client.

The Driver accepts every server certificate. The Server certificate field has no effect.

The Driver logs in to the server as an anonymous user, or with the Username and Password when you enter one of them. It cannot log in with a user certificate.

Connection options

Console label Python field Default Notes
Connect from rack The key of the rack that runs the Driver.
Endpoint endpoint opc.tcp://localhost:4840 Required in Python.
Username username Empty Empty for an anonymous login.
Password password Empty
Mode security_mode None "None", "Sign", or "SignAndEncrypt".
Policy security_policy None "None" goes only with the mode "None". See security policies.
Client certificate client_cert Empty A path on the Driver computer.
Client private key client_private_key Empty A path on the Driver computer. No password.
Server certificate server_cert Empty Has no effect.

In TypeScript, the fields are in properties.connection in camel case, such as securityMode, clientCertificate, and serverCertificate.

Security policies

Console label Value
Basic 256-bit with SHA-256 "Basic256Sha256"
AES 128-bit with SHA-256 "Aes128_Sha256_RsaOaep"
AES 256-bit with SHA-256 "Aes256_Sha256_RsaPss"
Basic 256-bit (deprecated) "Basic256"
Basic 128-bit RSA (deprecated) "Basic128Rsa15"

Troubleshooting

For other problems, see Troubleshoot hardware.